Identificador persistente para citar o vincular este elemento: https://accedacris.ulpgc.es/jspui/handle/10553/160808
Título: Wind power integration improvement in an island by installing battery energy storage systems. Case study of Lanzarote-Fuerteventura
Autores/as: Mejías García, L
Medina Padrón, José Fernando 
Medina Domínguez, Elías Jesús 
Clasificación UNESCO: 3308 Ingeniería y tecnología del medio ambiente
Palabras clave: Wind power
Isolated power system
Battery energy storage systems
Critical clearing time
Transient stability
Fecha de publicación: 2019
Publicación seriada: Renewable energy and power quality journal 
Resumen: Some small isolated power systems have a grid infrastructure weakly meshed and stability could be seriously affected when a large amount of renewable energy is being flowed into the grid. In this paper critical clearing time (CCT) is studied along with the increase in renewable energies integration. This study considers the use of squirrel cage induction generators (SCIG) wind turbines. Battery energy storage systems (BESS) have been considered in order to overcome this kind of power system drawbacks. Thus, renewable energy integration improvement is achieved. Renewable energy improvement is analyzed by means of CCT values. Dynamic analysis is performed in order to determine CCT values taking into account voltage, system frequency and the amount of load shedding.
URI: https://accedacris.ulpgc.es/jspui/handle/10553/160808
ISSN: 2172-038X
DOI: 10.24084/repqj17.246
Fuente: Renewable energy and power quality journal [2172-038X], v.17, (Julio 2019)
Colección:Artículos